Water chiller for blueberry maturing plant

The water chiller operates on two circuits. The first circuit is frequency controlled and the second operates on three stages. The plant cools the brine from -2° C to -6° C and takes care of the cooling of 15 fruit storage / maturing rooms.

Technical Data Overview:
Refrigeration Capacity Qo: 165 kW (1 compressor frequency controlled 30 - 60Hz)
Overall power consumption Pel: 99kW
Evaporating temperature to: -12 °C
Suction gas overheating toh: 10 K
Economizer operation
Condensing temperature tc: 45 °C
Refrigerant R404A

Evaporator:
Inlet temperature: -2 °C
Outlet temperature: -6 °C
Cooling medium: Wasser + 35% Prop.Glycole

Blueberry Maturing Plant
 
Economizer
 
The water chiller gets some shine
Water chiller buffer tank
 
Last screws to be tightened
 
Secundary pump station
Water Chiller
 
Water chiller with two cycles - liquid receiver station
 
Water Chiller 165 -2/-6
Water Chiller with Evaporator
 
Heavy Handling
 
Water chiller with primary pump
Maturing Smoking Water Chiller Unit:  (© www.frigopol.com)

Climatising - Maturing Smoking Water Chiller

This unit was designed for a meat processing industry application. The plant is used for the (pre-) maturing and smoking of raw sausages and meat products and includes two compact screw-compressors with liquid receiver and electronic panel system mounted.



Technical Data:
Refrigeration Capacity Qo: 231 kW
Evaporating Temperature to: -10 °C
Suction Gas Superheat toh: 10 K
Condensing Temperature tc: 50 °C
Refrigerant: R404A

WM Container 7:  (© www.digitalpix.at)

Water Chiller with Natural Refrigerant R717

Equipped with two open piston compressors, this water chiller is used for air-conditioning of an international airport.
Technical Data:
Refrigeration Capacity 50 Hz Qo: 306,4 kW
Evaporating Temperature to: +7 °C, Condensing Temperature tc: 37 °C

KWS EFr frontal:  (© www.frigopol.com)
KWS EFr schraeg offen:  (© www.frigopol.com)

NH3 Water Chiller

This water chiller with 3 semi-open separating hood compressors is used for air-conditioning of an international production site. The advantages of the unit filled with R717 are obvious: excellent thermo-dynamic characteristics and zero ozone-damaging potential. This is good for the enviroment and reduces the green house effect!

Technical Data:
Refrigeration Capacity Qo: 96,7 kW
Evaporating Temperature to: +2 °C
Suction Gas Superheat toh: 10 K
Condensing Temperature tc: 45 °C
Surrounding Temperature ta: 32 °C
Liquid Subcooling: 2 K

Kaltwassersatz Direktexpansion: Kaltwassersatz Direktexpansion (© www.frigopol.com)

Water Chiller with Natural Refrigerant

Highly environmental - friendly, this water chiller operates on the natural refrigerant ammonia. With dry direct expansion.

Technial Data:
Evaporating Temperature to = -13 °C
Condensing Temperature tC = +47 °C

Kaltwassersatz Turbocorverdichter: Kaltwassersatz Turbocorverdichter (© www.frigopol.com)

Water Chiller with 4 Turbocor Compressors

This ready-to-go unit is equipped with an electrical switch gear panel incl. controller system and operates on refrigerant R134a .

Technical Data:
Salt Spring Inflow: +12 °C, Salt Spring Exit: +6 °C
Capacity: 980 kW

вверх  |  печать   HOMEPAGE  |  SITEMAP


  IMPRESSUM | SITEMAP   FRIGOPOL - Kälteanlagen GmbH, Gamser Str. 21, A-8523 Frauental a.d.L
Tel. +43 (0) 3462 70 000, Fax +43 (0) 3462 70 000-50, office@frigopol.com